About the Bay Layout Area
Bay layout area calculation estimates the floor space required for each bay in a solar plant's HT switchyard — including equipment footprint (VCB panel, CT, PT, isolator, bus section), maintenance clearance, and access corridors — used for switchyard general arrangement (GA) drawing planning.
How to calculate it
- 1Typical bay dimensions at 11 kV (outdoor): width 3–4 m per bay; depth 8–12 m (from incoming line to the bus). Total area per bay: 24–48 m².
- 2At 33 kV: width 5–6 m per bay; depth 12–18 m. Total area: 60–108 m².
- 3Add control room: 12–20 m² for a 1–5 MW plant; 25–50 m² for 5–50 MW.
- 4Number of bays: one per feeder + one bus section bay + one transformer bay. For a 2 MW plant at 33 kV: incoming feeder (1) + transformer bay (1) + bus section (1) = 3 bays minimum.
- 5Total switchyard area ≈ bays × bay area + control room + access road within the switchyard (typically 4–6 m wide between rows of equipment).
Worked example
An 11 kV switchyard for a 2 MW plant: 3 bays × 4 m × 10 m = 120 m². Control room 15 m². Internal access road 50 m². Total switchyard area: ~185 m² (within a 15 m × 15 m plot boundary). Equipment layout: bus running east-west at 4 m height; VCB panels on concrete pedestals with 1.5 m front clearance.
What you can calculate
- Bay dimensions
- Total footprint
- AIS/GIS
- Voltage class
Frequently asked questions
Can a solar plant's switchyard be on the same plot as the solar array?
Yes — the switchyard is almost always within the solar plant's boundary, typically near the metering point/grid injection point. The DISCOM specifies the point of metering and the interface point; the developer provides the switchyard within their land boundary up to this point. For large plants (> 50 MW), a dedicated switchyard plot may be acquired adjacent to the main array area.
What is a gas-insulated switchgear (GIS) and when is it used for solar plants?
GIS uses SF6 gas insulation instead of air, reducing the switchyard's footprint by 70–80% compared to conventional air-insulated switchgear (AIS). GIS is used for solar plants in space-constrained locations (urban rooftop with HT connection, coastal sites, or where land cost is very high). GIS costs 2–3× more than AIS but the land saving can justify the premium. For most utility-scale solar plants in India, conventional AIS is used due to its lower cost and simpler maintenance.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
Step-Up Transformer Sizing
Calculate MVA rating, standard IS 2026 size, impedance and loss budget for solar grid step-up transformers
OpenTransformer Impedance & Losses
Calculate transformer impedance voltage, no-load/load losses and efficiency per IEC 60076
OpenPSS Busbar Sizing
Size substation busbars for continuous current, thermal limits and short-circuit withstand per IS 5082
OpenCT Sizing & Class Selection
Select current transformer ratio, accuracy class and knee-point voltage for protection and metering per IEC 61869
OpenPT / CVT Selection
Select voltage transformer or capacitor voltage transformer class, burden and accuracy for HV/EHV systems
OpenCircuit Breaker Rating
Rate circuit breakers for fault interrupting capacity, rated voltage and operating duty per IEC 62271
Open