About the Safe Working Clearance
Safe working clearance (SWC) defines the minimum distance between a person and a live electrical conductor or equipment to prevent electric shock or arc flash injury — essential for anyone working on or near energised solar, BESS, or substation equipment.
How to calculate it
- 1SWC depends on voltage level: at LT (< 1,000 V AC) — minimum 300 mm; at 11 kV — 900 mm; at 33 kV — 1,200 mm; at 132 kV — 2,000 mm (per IE Rules and IS 5216).
- 2These are approach boundaries, not working distances — work on energised HT equipment requires live-line tools and specialist training.
- 3For solar DC systems: although classed as LT (< 1,500 V DC), the DC shock hazard is higher than equivalent AC — maintain 500 mm minimum clearance from uninsulated DC conductors.
- 4Permit to Work (PTW) system: before any work near energised equipment, issue a formal PTW that specifies the safe isolation boundary, the SWC, and the permits required.
- 5Arc flash boundary: for HT equipment, calculate the arc flash incident energy (per IEEE 1584) and specify the arc flash protection boundary and PPE level.
Worked example
A maintenance technician accessing an AJB on a 500 kWp plant: DC system voltage 600–900 V. The AJB string fuses are at 900 V DC. SWC = 500 mm minimum from uninsulated busbars. Before opening the AJB: isolate the strings (open string fuse holders), verify voltage with a meter, then work. If working with the AJB energised (e.g., taking voltage readings): insulated gloves rated for 1,000 V DC and face shield required.
What you can calculate
- IE Rules 1956 Reg 64
- LT to HV
- Pass/Fail
- Safety margin
Standards & references
Frequently asked questions
Can solar panels be made safe for working on the roof?
Solar panels cannot be completely de-energised during daylight hours — they continue to generate DC voltage as long as light falls on them. To work safely: (1) block sunlight with opaque covers or work at night/overcast conditions; (2) isolate at the inverter DC isolator and AJB to remove current path; (3) use insulated tools and 1,000 V rated gloves. Never assume a panel is safe to touch without verifying with a calibrated DC meter.
What PPE is required for solar electrical work in India?
For LT work (< 1,000 V): insulated gloves (class 0 or 1, 500 V rated), safety glasses, and insulated hand tools (IEC 60900). For DC systems up to 1,500 V: class 1 or 2 gloves (rated 7,500 V), face shield, and fire-retardant clothing. For HT work (> 1,000 V): only licensed electrical workers with live-line training, rated HV gloves, hot sticks, and arc flash PPE may work on energised equipment. IS 5216 specifies these requirements.
Ready to build your solar project?
Get free quotes from verified EPCs and installers across India.
You might also need
Pedestal Height
Calculate front and rear pedestal heights for target module tilt on flat rooftops
OpenModule Layout Planner
Plan tables, rows and string configuration for a rooftop array
OpenSetback from Parapet
Calculate minimum module setback from parapet walls to avoid shading