About the DC Cable Sizing
DC cable sizing selects the conductor cross-section for string and array cables so the current rating is safe and the voltage drop stays within limits — typically kept under 1–3% on the DC side to avoid energy loss.
Formula
A = (2 × ρ × L × I) ÷ V_drop
- A
- Conductor cross-section (mm²)
- ρ
- Resistivity of the conductor (copper/aluminium)
- L
- One-way cable length (m)
- I
- Cable current (A)
- V_drop
- Allowable voltage drop (V)
How to calculate it
- 1Take the string/array current and the one-way cable run length.
- 2Set the allowable DC voltage drop (typically 1–3% of the operating voltage).
- 3Solve for the conductor size, then round up to the next standard cross-section that also meets the current-carrying (ampacity) rating.
What you can calculate
- IEC 60364-7-712
- Temp derating
- Voltage drop
- Ampacity check
Standards & references
Frequently asked questions
What voltage drop is allowed for solar DC cables?
DC cable voltage drop is usually kept below 1–3% at operating conditions. Lower drop means less lost energy but larger, costlier cable — 1% is common for main array runs, up to 3% acceptable for short string cables.
You might also need
AC Cable Sizing
Size AC cables from inverter to grid per IS 732 & IEC 60364 with full load current derating and voltage drop
OpenVoltage Drop
Calculate voltage drop % for DC and AC circuits and verify compliance with IEC & IS limits across the system
OpenShort Circuit Current
Calculate maximum DC and AC short-circuit current at each system point for protection device sizing
OpenFuse / MCB / MCCB Sizing
Select correct fuse rating, MCB curve, and MCCB interrupt capacity for DC strings, combiners, and AC outputs
OpenCombiner Box (AJB) Sizing
Size Array Junction Boxes with string count, fuse ratings, SPD specification, and busbar current capacity
OpenDCDB Sizing
Size DC Distribution Boards with main MCCB, busbar, SPD, monitoring, and enclosure IP rating selection